Description
Wall Mount Battery , vertically stackable, side cover on battery opens up and conceals all wiring, cables to link battery to battery are included
Instructions for MPP Solar Inverters (LVX6048, LV6548) Set Protocol to “LIB” on inverter. (see attached pictures for settings)
Use supplied BMS Comms cable (pins 1 and 2 on battery go to pins 3 and 5 on inverter BMS port [ 1 to 3, 2 to 5])
Set battery address dial to “0”, install RS485 termination plug (supplied) into one of the inter battery RS485 comm ports (see pics)
and thats it.
This battery can be used in “dumb” mode – no comms with any other 48V battery system in order to increase battery capacity, and on any 48V inverter
battery Manual:
https://www.mppsolar.com/v3/catalogs/ESS8K.pdf
http://www.mppsolar.com/manual/ESS_LITHIUM/ESS810A-manual-20221125.pdf
battery LED Status:
https://www.mppsolar.com/manual/ESS_LITHIUM/LIO%20II-4810E-manual-20240126.pdf
BATTERY
Nominal DC Voltage: | 48 VDC |
Maximum Charging Current: | 120 A |
Dimension: | (D x W x H): 8.4″ x 24.4″ x 19.7″ |
Net Weight: | 99 lb |
Capacity: | 5120Wh |
Nominal Voltage: | 51.2VDC |
Full Charge Voltage(FC): | 56V |
Full Discharge Voltage(FD): | 42V |
Typical Capacity: | 100 Ah |
Max Continuous Discharging Current: | 120A |
Max Discharging Current: | 192A at 1 min |
Protection: | BMS, Breaker |
Float Charge Voltage: | 52.5V |
Charge Current: | 20A (0.2C) |
Maximum Charge current: | 50A (0.5C) |
Standard Charge method: | 0.2C CC (Constant current) charge to FC, CV (Constant voltage FC) charge till charge current declines to <0.05C |
Inner Resistance: | ≤20m ohm |